CAPM-2 Carrier Frequency Pickup Module
Installation & Technical Guide
Installation:
Ensure that the flow meter sensor cavity is free of debris prior to installation.
Screw the CAPM-2 into the flow meter by hand until the sensor nose contacts the bottom of the cavity.
Do not screw in harder than hand tight, as a thin metal section is under the sensor nose.
Please heed the following warning:
CAUTION: DO NOT EXCEED 7 NEWTON-METERS FORCE TO SEAT THE SENSOR, THIS IS
EQUIVALENT TO HAND TIGHT. EXCESS FORCE MAY CRUSH THE SENSOR NOSE OR
DAMAGE THE FLOW METER BY FORCING THE METAL SECTION UNDER THE SENSOR INTO
THE MEASURING CHAMBER.
Wiring should be installed by a qualified instrumentation technician.
Some basic installation guidelines are reviewed overleaf.
Description:
The CAPM-2 is a Carrier Frequency sensor, which means there is no permanent magnet in the
pickup, and any magnetic drag on the flow meter is avoided. The CAPM-2 requires a supply voltage
between 10 VDC and 30 VDC. A diode in the supply input prevents damage to the module in case
the polarity of the supply voltage is wrong. The output signal is a square wave, voltage pulse of
approximate amplitude (supply – 1.5 V). The frequency is proportional to the flow rate.
The output is a sourcing open collector transistor (PNP Type).
An NPN sinking type is available and is designated as CAPM-2N.
Technical Data
Supply Voltage: 10 to 30 VDC
Supply Current: 9 mA @ 15 Volt, Max 18 mA
Minimum Signal: 0.5 Hz
Signal Output: Square wave, V
High
V
CC
- 1.5V
V
Low
0V
Duty Cycle: 50%
Frequency Output: Flow dependent, up to 2000 Hz
Load: >500
Driving Capacity: 10 mA Max
Temperature Range: -60°F to 185°F (-50°C to 85°C)
Connections:
A = +10 to 30 VDC supply voltage
B = Ground for supply and signals
C = Frequency signal output
Note: If signal does not go to ground, connect
external resistor, 5 K-10 Kohm, between input and
ground of monitoring equipment.
Figure 1
AW Wiring Color Code:
Supply Voltage: Red
Ground: Black
Signal: White